What is the requirement of the flash point value of phosphate ester against fuel used in power plant?

latest company case about What is the requirement of the flash point value of phosphate ester against fuel used in power plant?  0

 

 

According to DL/T 571-2014 Phosphate resistant fuel operation and Maintenance Guidelines for power plants, flash point requirements of new phosphate resistant fuel are as follows: Open flash point requirements :≥240℃

In operation, phosphoric acid value and fuel flash point value requirements are as follows: open flash point requirements :≥235℃

According to DL/T 571-2014 Phosphate ester fuel resistance Operation and Maintenance Guidelines for power plants, flash point value is measured by GB/T3536, SH106B automatic open flash point tester. Is in accordance with the People's Republic of China standard GB/T 3536, GB/T267 "petroleum products flash point and flash point determination (Cleveland opening cup method)" the requirements of the design and manufacture also support GB/T1671-2008 plasticizer flash point determination ASTMD92.

Open flash point is mainly used to measure gasoline engine lubricating oil, diesel engine lubricating oil, compressor oil, refrigeration

Engine oil, steam turbine oil, gear oil, mechanical oil, oil resistance, etc

 

Main technical index and parameter and characteristic

1, the instrument adopts color LCD large screen display, Chinese man-machine dialogue interface, no identification keyboard, to pre-value temperature, sample label, atmospheric pressure, test date and other parameters, with a prompt menu, guided input function.

2, simulation tracking display temperature rise and test time function curve, with Chinese error operation software prompt modification function, with test date, test time and other parameters prompt function.

3. Automatically correct the influence of atmospheric pressure on the test and calculate the correction value.

4, differential detection, automatic correction of system deviation.

5. Scan, detect and print data automatically, and the test arm automatically rises and falls.

6, electronic ignition, forced air cooling

7, automatic ignition without air source, improve the safety of the test

8, working power supply: AC220V±10%, 50Hz

9, temperature measurement: range: room temperature ~ 400℃;

Repeatability: flash point ≤150℃ error ±2℃ flash point ≥150℃ error ±3℃

Resolution: 0.1℃; Accuracy: 0.5%;

10, heating rate: in line with GB/T3536 standard;